Reliant EMC

Mono/Double output Power Supplies

dp series

 

TECHNICAL DATA

  • Mains Input
    115 or 230 Vac ± 10% 48-400 Hz
  • Line regulation
    better than 50 ppm of output V max for the allowed input variation
  • Voltage and Current Output
    adjustable by a 10 turns potentiometer from “0” to max rated
  • Load regulation for constant V
    from no load to full load better than 50 ppm
  • Load regulation for constant I
    better than 100 ppm of I max from “0” to V max .
  • Ripple and noise
    lower 30 ppm (rms) of V max, measured in V mode
  • Recovery time
    better than 20µs within ± 1% of set voltage from no load to full load.
  • Reaction to remote programming (slew rate)
    1V / µs
  • Stability
    after 20 minutes of preheating, better than 0.1% for 24 hours at 25°C ambient
  • Temperature coefficient
    lower 50 ppm/°C in “voltage mode”;
    lower 100 ppm/°C in “current mode”
  • Ambient temperature
    work 0÷40°C
    storage -10÷50°C
  • Cooling
    forced air
  •  
DANA Mono Double output

DANA Mono Double output

 

FRONT PANEL CONTROLS

Power
switches equipment ON and OFF
DC
enables DC output through a dedicated switch (in dual models DCM Master and DCS Slave)
Check
V - A - OVP set up push-buttons when the Power Supply is in stand-by
Section V
Potentiometer and display (with accuracy of 1.5%) showing output voltage or, by means of Check button, programmed voltage.
Section A
Potentiometer and display (with accuracy of 1.5%)
showing output current or, by means of Check button, programmed current.
OVP (Over Voltage Protection)
trimmer allowing to set up “hazard-limit” for the EUT, when picked it up inhibits Power Supply with an alarm LED lighting up
OT
Over-temperature alarm of power circuit that puts Power Supply in stand- by mode with an alarm LED lighting up until the end of over temperature
Remote
Slider switches selecting working mode of Power Supply from “local programming” to “remote programming” with a LED showing “remote” function
Master/Slave (Dual output models only)
switch allowing the function connecting controls of two sections in an optically isolated mode. It also allows parallel or series of the two power sections, in local as well as in remote mode
M/S
trimmer allowing to get two separate outputs from the power supply with same or different voltages between 100/100 and 100/50 rate
 

BACK-PANEL CONTROLS

Terminal block allowing to switch “remote sense” circuit control from power output plugs to remote sense, to recover a max voltage drop of 0,5 V for cable
GPAC
“General Purpose Analog Control” connector to program remotely the Power Supply with 0 ÷ 10 Vdc analog voltage for all his functions and to read feed-back (0 ÷ 10 Vdc) proportional to output Voltage and Current.
 

Options

PS / PW
interface to program the Power Supply with IEEE488/RS232 or IEEE488/RS485 standard (with increased dimensions)
O
optically isolated controls for remote commands and feed- back
R
ears for rack mounting
DIMENSIONS
Width: ½ rack = 222mm – rack = 444mm
Height: 2U rack (89 mm)
Depth: 365mm (all models)
 
DANA DP2C 100-4 PS2 External
 
DANA DP2C 100-4 PS2 Internal

 

DANA DP Linear AC DC Mulit Output Power Supplies Model Chart
DANA DP Linear AC DC Multi Output Power Supplies Model Chart
 
The models in the table are available with voltage and output current on customer request

 

3 year Warranty!

 

Associated Downloads

 

· Request a Quote / Contact Us!

DANA Power Supplies

 

DANA S.r.l. Power Supplies

Reliant EMC Product Lines